HOS-AK1 Hall Effect Sensor

The HOS-AK series of panel mounted, split-core, open loop, Hall Effect current sensors are designed for applications requiring the measurement of DC current and DC current pulses.

Features:
  • Primary Conductor opening – 40mm (1.57″).
  • Split-core design.
  • Contact-less, non-intrusive current sensing.
  • DC current, DC pulse and AC current measurements.
Model Rated Current (A RMS) Measurement Range (A)
HOS-100AK1 100A 0 to ± 150A
HOS-200AK1 200A 0 to ± 300A
HOS-400AK1 400A 0 to ± 600A
HOS-600AB 600A 0 to ± 900A
HOS-800AK1 800A 0 to ± 1200A
Performance:
  • Accuracy: ± 1% Nominal Current
  • Linearity: ≤ 1%
  • Response Time: ≤ 10µSecond
  • Offset Voltage (@ +25°C): ± 30mV maximum for primary current In = 0.
  • Temperature Drift: ± 1mV/ °C maximum (-10 °C to +70 °C)
Specifications:
  • Frequency: 0 to 20kHz.
  • Dielectric withstand voltage between Primary and Secondary: 5,000V RMS @ 50HZ for 1 minute.
  • Load resistance: > 10 kOhms .
  • Operating Temperature: -10ºC to +85ºC.
  • Storage Temperature: -15ºC to +90ºC.
  • Supply Voltage: ±12V … 15V (± 5%).
  • Supply Consumption: 25mA.
  • Construction:
    • Epoxy encapsulated housing.
    • Case material – Nylon, UL flame retardant rating 94 V-0.
  • RoHS Compliant

Physical Specifications:

HOS-AK1

Download HOS-AK1 Brochure (pdf 276kb)



Many of our products can be designed and manufactured to meet the specific application requirements. For a no obligation technical evaluation, please provide the specific performance requirements to engineering@tichenassociates.com.