35mm Mini Split-Core Current Transformer

The CTSA family of mini split-core current transformers offers fast and easy installation into existing AC electric distribution systems where space is a premium. The split-core current transformers feature a high performance magnetic core in a small physical package. The robust packaging features a mechanical hinge for multiple open/ close actions, tight fitting of the mating core halves and secure closure of the current transformer after installation. This feature insures consistent and highly accurate performance over the life of the current transformer. The robust CTSA split-core current transformer design, manufactured in an ISO9001 certified manufacturing facility, insures many years of defect free operation backed by a strong product warranty of 36 months.

Features:
Typical Models Rated Current (Ampere) Accuracy Class
CTSA035-200A/ 0.333V or mA option 200A 0.5/ 1.0
CTSA035-300A/ 0.333V or mA option 300A 0.5/ 1.0
CTSA035-400A/ 0.333V or mA option 400A 0.5/ 1.0
CTSA035-500A/ 0.333V or mA option 500A 0.5/ 1.0
Performance:
  • Accuracy Class: 0.5, 1.0 (IEC 60044-1)
  • Accuracy: < 1% error
  • Phase Angle: < 60 minutes
  • Linearity: ±1% from 5% to 120% of rated primary current
Specifications:
  • Input Frequency: 50 to 400 HZ
  • Maximum Primary Voltage: 720 VAC
  • Dielectric Withstand Voltage: 2,500V for 1 minute
  • Dielectric Resistance: 100 MOhms @ 500 VDC
  • Operating temperature: -15ºC to +60ºC
  • Construction:
    • Opening: 35.2mm (1.39″)
    • Core material: Silicon steel CRGO (cold rolled grain oriented)
    • Epoxy encapsulated
    • Case: Nylon UL flame retardant rating 94V-0
  • Standard Leads: 0.61m (2 ft.), UL 1015, twisted pair, 0.34mm2 (22AWG)
  • RoHS Compliant
Physical Specifications:
Dimension mm (in)
L W H ID
56.4mm (2.22″) 40.8mm (1.61″) 83.8mm (3.30″) 35.2mm (1.39)
Download CTSA035 Data Sheet (pdf 238kb)



Many of our products can be designed and manufactured to meet the specific application requirements. For a no obligation technical evaluation, please provide the specific performance requirements to engineering@tichenassociates.com.