CTSB0812 Split Core Current Transformer

Split-core current transformer

The CTSB series of split-core current transformers are designed for the measurement of AC currents carried by large primary conductors or substation BUS bars.The split-core design permits the fast and easy installation on large primary conductors/ substation BUS bars without requiring that the primary conductor be taken offline and disconnected for CT (current transformer) installation.
The CTSB series of split-core current transformers feature a high performance magnetic core for highly accurate AC current measurement. The robust packaging features;

These features insures consistent and highly accurate AC current measurement performance over the life of the current transformer installation.
The robust CTSB split-core current transformer design, manufactured in an ISO9001 certified manufacturing facility, insures many years of defect free operation backed by a strong product warranty of 36 months.

Features:
Nominal Current Ratio Accuracy Class
(max burden)
Linearity
500A:5A 1.0 (5.0ohm) 10% to 130%
600A:5A 1.0 (5.0ohm) 10% to 130%
750A:5A 0.5 (3.7ohm) 10% to 130%
1000A:5A 0.5 (5.0ohm) 10% to 130%
1250A:5A 0.5 (7.5ohm) 10% to 130%
1500A:5A 0.5 (7.5ohm) 10% to 130%

Specifications:

  • Input Frequency: 50/ 60 HZ
  • Accuracy Class: 0.5, 1.0, 3.0
  • Phase Angle: less than 2 degrees at 50% of rated current
  • Linearity: ±1% from 10% to 130% of rated primary current
  • Insulation Voltage 720 Vac
  • Maximum Primary Voltage 5,000Vac (insulated conductor)
  • Operating temperature: -15ºC to +60ºC
  • Construction:
    • Epoxy encapsulated
    • Case: Nylon UL flame retardant rating 94V-0
  • RoHS Compliant


Physical Specifications:
Dimension mm (in)
A B C D E
80.0 (3.1) 120.0 (4.7) 108.0 (4.3) 144.0 (5.7) 185.0 (7.3)
Dimension mm (in)
F G H I
32.0 (1.3) 32.0 (1.3) 32.0 (1.3) 33.0 (1.3)

Download CTSB Brochure (pdf 349kb)
CTSB InstallationInstallation instructions (664kb)