CTSB0816 Split Core Current Transformer

Split-core current transformer

CTSB Split-Core Current Transformers – Designed for fast and easy installation on large primary conductors/ substation BUS bars. The split-core design permits non-contact AC current measurements without requiring that the primary conductor be taken offline and disconnected for CT installation.

Features:
  • Primary Conductor opening – 80mm(3.2″) x 160mm(6.3″).
  • Secondary Current Output Options:
    • 5A or 1A.
  • Secondary Voltage Output Options:
    • 0.333V, 0.500V, 0.666V,
    • 1.000V, 2.000V, 3.530V,
    • 5.000V
Current Ratio Accuracy Class
(max burden)
Linearity
500A:5A 1.0 (5.0 ohm) 10% to 130%
600A:5A 1.0 (5.0ohm) 10% to 130%
750A:5A 0.5 (5.0 ohm) 10% to 130%
1000A:5A 0.5 (10.0 ohm) 10% to 130%
1500A:5A 0.5 (15.0 ohm) 10% to 130%
2000A:5A 0.5 (15.0 ohm) 10% to 130%
2500A:5A 0.5 (15.0 ohm) 10% to 130%
3000A:5A 0.5 (20.0 ohm) 10% to 130%
4000A:5A 0.5 (20.0 ohm) 10% to 130%
5000A:5A 0.5 (20.0 ohm) 10% to 130%

Specifications:

  • Input Frequency: 50/ 60 HZ
  • Accuracy Class: 0.5, 1.0, 3.0
  • Phase Angle: less than 2 degrees at 50% of rated current
  • Linearity: ±1% from 10% to 130% of rated primary current
  • Insulation Voltage 720 Vac
  • Maximum Primary Voltage 5,000Vac (insulated conductor)
  • Operating temperature: -15ºC to +60ºC
  • Construction:
    • Epoxy encapsulated
    • Case: Nylon UL flame retardant rating 94V-0
  • ETL Certified (Control #4002689)
  • RoHS Compliant


Physical Specifications:
Dimension mm (in)
A B C D E
80.0 (3.1) 160.0 (6.3) 120.0 (4.7) 184.0 (7.2) 245.0 (9.6)
Dimension mm (in)
F G H I
52.0 (2.0) 52.0 (2.0) 52.0 (2.0) 38.0 (1.5)
Download CTSB Data Sheet (pdf 515kb)



Many of our products can be designed and manufactured to meet the specific application requirements. For a no obligation technical evaluation, please provide the specific performance requirements to engineering@tichenassociates.com.